Loading...
HomeMy WebLinkAbout1997-10-02 ORDINANCE NO. 97-10-2 ORDINANCE MODIFYING BATESVILLE ORDINANCE NO. 95-1-2 AND SETTING FORTH CERTAIN MODIFICATIONS OF THE WATER UTILITIES CROSS CONNECTION CONTROL PROGRAM WHEREAS there are modifications necessary to the Batesville Water Utilities Cross Connection Control Program established under Batesville Ordinance no. 95-1-2 mandated by law and formalization of policy and procedure for the regulation of Cross Connections by the City of Batesville; THEREFORE, be ordained by the City Council of the City of Batesville, Arkansas: Section 1 Batesville Ordinance no. 95-1-2 is modified in the following particulars: 1.3 DEFINITIONS shall be modified as follows: The following terms shall have the stated meanings: A. Approving Authority means the Manager of the BWU or his designated agent(s). B. Auxiliary Water Supply means any water supply, on or available to the property other than the Water System. • C. AVBA means Atmospheric Vacuum Breaker Assembly. D. AWWA means American Water Works Association. E. Backflow means flow of water or other liquids, mixtures or substances, under positive or reduced pressure into the distribution pipes of a potable water supply from any source other than its intended source. F. Backflow Prevention Assembly ( or "Assemblies':) means a mechanical backflow preventer assembly constructed with shut-off valves, and provided as a complete assembly by a single manufacturer, used to prevent the backflow of contaminants or pollutants into the Water System. The assembly must have the approval of the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California, the State of Arkansas Department of Health, and the City. G. Backflow Prevention Device means a mechanical device used to prevent the backflow of water. H. BWU means the Batesville Water Utilities. O1 l • I. Bypass means any arrangement of pipes, plumbing, or hoses designed to divert the flow around an installed device or assembly through which the flow normally passes. J. Certified Testing Technician means a person certified by the Arkansas Department of Health as an Assembly Testing Technician. K. Certified Repair Technician means a person certified by the Arkansas Department of Health as an Assembly Repair Technician. L. lily means the City of Batesville, Arkansas. M. Consumer means a "person" or "facility" receiving service from a potable water system. N. Contaminant means a biological agent or chemical compound which can cause disease or threat to health. O. Cross Connection means any actual or potential connection between the Water System and a source of contamination or pollution. • P. Cross Connection Control means the use of backflow prevention assemblies, methods and procedures to prevent contamination or pollution of a potable water supply through cross connections. Q. Degree of Hazard means the relative classification of the danger posed by a particular substance or set of circumstances. R. Domestic refers to plumbing as defined by the State of Arkansas Plumbing Code that is not associated with designated fire protection water service lines and systems. S. Double Check Valve Assembly (DCVA) means a backflow prevention assembly consisting of two independently operating check valves, 4 test cocks, and 2 shut- off valves. DCVAs are only appropriate for use against non-health hazards. DCVA can be subjected to backpressure. T. Detector Double Check Valve Assembly (DDCVA) means a DCVA with an additional smaller DCVA with a flow detector meter in parallel, used to detect system leaks and unauthorized use. Assembly must be shipped as a complete unit. • 2 U. Detector Reduced Pressure Zone Assembly (DRPZA) means a RPZA with an additional smaller RPZA with a flow detector meter in parallel, used to detect system leaks and unauthorized use. Assembly must be shipped as a complete unit. V. Fire Protection System means a fire protection system,consisting of one or more of the following: Pipes, sprinklers, valves, fixtures, fittings, ponds, tanks, water storage vessels and fire hydrants that are intended and used exclusively for fire protection. W. Hose Bib Vacuum Breaker (HBM For all residential and non residential hose supply outlets not subject to continuous pressure. X. "Hot Box" is the Trade Mark for an above ground backflow prevention assembly enclosure incorporating freeze and vandalism protection features and as used herein is a standard for definition of the type and specification of enclosure. Y. Inspector means a person authorized by the Approving Authority to perform inspections of consumer's facilities to determine compliance with the Ordinance. Z. Isolation means the actual or physical separation of a specific section of plumbing within a premises by the means of an air gap or mechanical device. AA. Multiple Services means two or more water service connections. When two or more water suppliers are involved, the multiple service connections constitute an "auxiliary source" of water on the property. BB. NFPA Pamphlets means "National Fire Protection Association" pamphlets. CC. New Construction means construction of a new facility, alteration of or addition to an existing facility, or modification of or addition to existing plumbing and fire protection systems. DD. Person means any individual, partnership, company, public or private corporation, political subdivision or agency of the United States or any other legal entity. EE. Pollutant means a biological or chemical substance which does not pose a health hazard but reduces the aesthetic quality of water. • 3 FF. Pressure Vacuum Breaker Assembly(PVBA) An assembly consisting of an independently operating internally loaded check valve, an independently operating loaded air inlet valve located on the discharge side of the check valve, with properly located resilient-seated test cocks and tightly closing resilient-seated shutoff valves attached at each end of the assembly designed to operate under pressure for prolonged periods of time to prevent backsiphonage. The pressure vacuum breaker may not be subjected to any back pressure. GG. Program means the Batesville Water Utilities Cross Connection Program. HH. Responsible Managing Employee (RNIE) means an individual or individuals who shall be designated by each company that plans, sells, installs, maintains, or services a fire protection sprinkler system on a full time basis to assure that each fire protection sprinkler system as installed, maintained, or serviced meets the standards as provided by state law. II. Reduced Pressure Zone Assembly (RPZA) means a backflow prevention assembly consisting of four test cocks, two shut-off valves, two independently operating, spring loaded check valves with a reduced pressure zone between the checks valves. The zone contains a relief port which will open to atmosphere if the pressure in the zone falls within 2 psi of the supply pressure. The assembly provides protection against both backpressure and backsiphonage. JJ. Retrofit means replacement of an existing device or backflow prevention assembly when the specifications or condition of the device or assembly are not adequate for the degree of hazard found on the property as defined by this program. KK. Service Connection means a piping connection between the water main of BWU and a consumer's system. LL. UL means Underwriter Laboratories. Section 2.0 AUTHORITY OF APPROVING AUTHORITY shall be modified to read as follows: The Approving Authority shall administer the Program, and may designate individuals to conduct the Program. A. The Approving Authority is hereby authorized to: • 4 • (1) To protect the public potable water distribution system from contamination or pollution due to the backflow or backsiphonage through the water service connection. (2) Conduct a program which includes routine inspection of commercial, institutional, industrial establishments, and residential sites for possible contamination or pollution. (3) Require installation of a backflow prevention assembly depending on the possible degree of hazard. (Whether direct or indirect.) (4) Review construction plans and determine requirement for backflow prevention assemblies. This shall apply to new construction, alteration or additions, as well as, modification of existing fire protection systems. This authority in no way infringes upon, and is in addition to the authority of the Batesville City Enforcement Officer with regard to his duties in plan review and approval. (5) Provide installation criteria for backflow prevention assemblies prior to construction. (6) Conduct final inspection of backflow prevention assembly installations to verify conformance with approved installation plans. (7) Ensure that RPZAs used for fire hydrants are performance tested. (8) Maintain RPZAs and meters for issue to water users needing temporary water service from fire hydrants. (9) Ensure RPZAs used by customers are tested annually and before issue. (10) Verify fire hydrant RPZAs and meters are set and removed by BWU Personnel. (11) Submit all required reports, maintain a data base, coordinate with other agencies to accomplish the purposes set forth in paragraph 1.2 and maintain the following records: (a) Master files on customer Cross Connection Tests. (b) Copies of lists and summaries available to the State Health Department. • 5 (c) Number of annual tests conducted on backflow prevention assemblies. (d) Number of cross connection control surveys performed. (e) Total number of each type of backflow prevention assemblies that are installed. (f) The following information is required per assembly. DDCVA and DRPZA are made up of two assemblies, each requiring record data. (i) Customer's name, mailing address, contact name, assembly address. (ii) Type installation, problem history, location on property, and type of service. (iii) Name of the manufacturer, model number and serial number of assembly. (iv) Type of assembly, date of installation (if available) and • installation specifications. (v) Date of initial cross connection survey, survey results and type of actual or potential hazard. (vi) Test results before and after repair or maintenance and date of latest retest. (vii) Maintenance performed, repairs made, replacement parts, date repairs were made. (viii) Information on backflows through the assembly. (12) Maintain an inventory of all residential, commercial, institutional and industrial locations with complete information on cross connection devices or assemblies installed. (13) Ensure meters on fire protection assemblies are read and consumer advised of water usage. ® 6 (14) Ensure a Certified Assembly Repair Technician is responsible for all repairs performed on an assembly. Installing backflow prevention assemblies within the scope of the plumbing system, shall be in accordance with the Arkansas Plumbing Code. (15) Verify only Certified Assembly Testing Technicians perform testing on backflow prevention assemblies. Section 2.7 INSPECTION FREQUENCY shall be modified to read as follows: All such facilities should be inspected by the approval authority on the following schedule: A. High Hazard - Once per year. B. Low Hazard - Once every five years. Section 2.8 CATEGORIES OF POTENTIAL CROSS CONNECTION HAZARDS shall be modified to read as follows: All commercial, institutional, industrial establishments, and residential sites having potential cross connection hazards categorized by the Approving Authority into one of the three following categories: A. High Hazard a condition, device, or practice which is conducive to the introduction of water borne disease organisms, or harmful chemical, physical, or radioactive substances into a public water system, and which presents an unreasonable risk to health. B. Low Hazard a hazard which does not pose an immediate unreasonable risk to health, which could cause aesthetic problems or have a detrimental effect on the quality of the public potable water supply. Section 4.3 DCVA AND PVBA CONTAINMENT shall be modified to read as follows: An approved DCVA or PVBA may be the minimum backflow prevention required in the water service line if the owner can document that there are no potential high hazards on the premises. 7 A. Buildings Any multi-story building, hotel, apartment house, public or private structure if a booster pump is used on the premises, or it is expected that a piping or equipment change might be made that could result in a cross connection to a low hazard. B. Establishments Any establishment containing chemical or biological pollutants. C. Interconnected Water Services If there is a potential for two or more water service lines being interconnected, and all water is used domestically, and only water from the Water System is available to the premises. D. Private Water Systems If there is an auxiliary water supply on or available to the premises, including a fire protection system. Section 4.4 HOSE BIB VACUUM BREAKER CONTAINMENT (HBVB) shall be modified to read as follows: A HBVB device shall be utilized on all premises for isolation and back siphonage only. Section 4.5 CONTAINMENT NOT REQUIRED shall be modified to read as follows: • Backflow prevention shall not be required in the water service line if the owner can document that there are no potential hazards on the premises, that the owner has provided isolation in their facility and the Water System complies with all applicable requirements of the City and State of Arkansas, and the Water System conforms to one of the following: A. Residential Systems Used exclusively for domestic purposes, unless the system includes a permanently installed yard sprinkler system. B. Solar Heating Systems Used exclusively for once through heating (i.e. domestic hot water), and no chemical additives are used in the system. • 8 Section 4.7 D shall be modified to read as follows, and Section E and F, shall be added as follows: D. Retrofit Of Existing Systems This applies to an existing fire protection system which is being modified, extended, or enlarged. Such systems include a modification or extension to an existing network such as (distribution piping, sprinkler heads, control valves, etc. are added to an existing system), or where an additional fire protection system (new feed line, riser, control valve, distribution piping, sprinkler heads, etc.) is added to an existing system. If any of the conditions are met the system will be required to be upgraded to meet minimum standards E. The installation of properly sized assembly may cause an excessive pressure loss in some altered Class 1 and 2 systems. Such loss could make the system noncompliant with NFPA Pamphlets 13 and 14 as adopted. The Responsible Managing Employee shall document to the Approving Authority that reasonable modifications will not compensate for the additional loss. The documentation shall contain a listing of the minimum flow and pressure, headloss summary, desired and calculated sprinkler head output and a summary of the options examined to reduce headloss. For these installations, if not already installed, the existing cross connection control device will be replaced with two check valves in series (one of which can be the alarm valve), each valve meeting AWWA C508-82, UL 312-88, • or UL 193-88, or the latest versions thereof, and equipped with a resilient seating surface. The valves or adjacent piping shall be equipped with a sufficient number of resilient seated test cocks (minimum diameter of one quarter to one-half inch) to determine the effectiveness of each valve (there shall be no leakage past any check valve). Sufficient resilient seated isolation valves - one valve upstream of the valves and one valve downstream of the valves - shall be present or added to the system to permit this testing. F. Existing Systems Existing fire protection systems, which have no single check valves or alarm valves are required to meet the minimum standards for a Class 1 and 2 fire protection system. The minimum protection for cross connection control for existing systems is the same as listed for new systems, except for existing systems which have a minimum of a single check valve. The check valve must have 2 resilient seated test cocks installed, one up stream and one downstream of the valve to determine the effectiveness of the valve. The performance testing of the check valve shall be preformed at intervals predetermined by the Approving Authority. Should a check valve fail during any performance test, it will automatically be subject to upgrade to meet the minimum for protection requirements. 9 Existing fire protection systems which have a Class 4, 5, or 6 rating must have at a minimum a DRPZA installed on either the main riser or it can be installed on the chemically effected section of the piping system. Section 4.8 CONSUMER RESPONSIBILITIES shall be modified to read as follows: The consumer shall: A. Eliminate all cross connections or install an approved backflow prevention assembly on the water service line. B. Immediately correct any malfunction of the backflow prevention assembly. C. Inform the Approving Authority of any proposed or modified cross connections and of any existing cross connections of which the consumer is aware. D. Submit construction plans for approval, and install an approved backflow prevention assembly. Failure, refusal, or inability on the part of the customer to install, maintain, and have tested, any backflow prevention assembly on the consumer's property shall constitute grounds for discontinuing water service until such requirements have been satisfactorily met. E. Have the type of backflow prevention assemblyand manner of installation approved by the Approving Authority. F. Install a backflow prevention assembly if a private water source is operational even if it is not cross connected to the Water System. G. Install two (2) backflow prevention assemblies in parallel if uninterrupted water service is desired during testing or repair. H. Not install a by-pass around any backflow prevention assembly unless there is a backflow prevention assembly of the same type in the bypass. I. Have a certified operational test within 10 days of installation. All RPZA's, DCVA's, PVBA's, DRPZA's, and DDCVA's will be tested at intervals not to exceed one (1) year after installation and annually there after. In those instances where the Approving Authority deems the degree of hazard to be great, an operational test may be required at more frequent intervals. I 10 J. Have only personnel licensed by the Arkansas State Health Department accomplish repairs, installation, maintenance and testing of backflow prevention assemblies. Assemblies for fire protection lines tapped from a domestic service line shall meet the same criteria. Repairs shall be made immediately upon notification by the tester. Overhaul shall be accomplished at intervals not to exceed five (5) years. Section 5.1 BACKFLOW PREVENTION ASSEMBLIES shall be modified to read as follows: Only those assemblies that are approved by BWU shall be used for backflow prevention in water service lines. A. Approved Assembly: Assemblies that have been tested and approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California and certified by the Arkansas Health Department are approved by BWU. B. The following information shall be distinctly marked on every RPZA, DCVA, PVBA, DDCVA and DRPZA by cast in the metal, stamped in the metal, or stamped on a brass or stainless steel nameplate permanently affixed to the assembly: • (1) name or trademark, (2) type (RPZA, PVBA, DDCVA, DRPZA, DCVA), (3) size, (4) model number, (5) direction of flow (indicated by an arrow), (6) serial number, (7) maximum working water pressure, and (8) maximum water temperature for which designed (designate degree F or degree C). C. Every RPZA, DCVA, PVBA, DDCVA and DRPZA shall be shipped from the manufacture completely assembled. 11 I Section 6.2 Shall be deleted in its entirety Section 6.3 INSTALLATION DETAIL shall be renumbered 6.2 and modified to read as follows: A. Assembly Installation A backflow prevention assembly shall be installed in accordance with the manufacturer's instructions. (1) An assembly shall be installed on the owner's side of the water meter prior to first outlet, unless isolation is used. (2) Piping connected to the assembly shall not be used for electrical grounding. (3) Piping connected to the assembly shall be thoroughly flushed before installing the assembly. (4) An adequate and permanent method of test water disposal shall be provided. (5) A pressure relief valve shall be properly installed and maintained on all water heating apparatus served by the assembly. (6) The assembly installation shall be protected from vandalism and freezing. (7) Adequate support, excluding water lines, shall be provided for assemblies that are 3" or larger. (8) If not part of the approved assembly, an approved strainer should be installed on the inlet side of the assembly prior to the assembly isolation valve, so that all water must pass through the strainer immediately before entering the assembly. (9) An approved blow-off shall be installed on stagnate flow 4-inch or larger water lines immediately after the assembly, to allow for flushing the assembly. Four-inch through ten-inch assemblies shall have a blow-off not less than 2-inches in diameter. Assemblies larger than 10-inch shall have a minimum 4-inch blow-off Blow-offs installed in vaults shall have piping into the existing vault drain to prevent splashing. Blow-offs in vaults may also be routed above grade and away from the vault, however, a self draining feature must be incorporated to prevent freezing damage to the blow-off piping. 12 • (10) If the assembly cannot be installed in the prescribed manner for any reason, the proposed deviations shall be submitted to BWU for review and approval before installation. B. RPZA DRPZA DDCVA, DCVA Installations (1) The assembly shall not be installed below grade, unless the following criteria can be met and accepted by the Approving Authority: (a) The vault and its installation shall be approved by BWU before the start of construction. In no case shall the vault be deeper than four (4) feet. (b) The vault shall not be subject to flooding. (c) The walls of the vault shall extend above the finished grade a minimum of 3" to prevent intrusion of water or dirt. (d) The vault shall be water-tight to prevent intrusion of water or dirt. (e) The vault shall drain to daylight through an adequate and permanent gravity drain with a slope of at least 1 degree. Installation plans shall show the elevation of the vault floor and the area the water will drain to. Plans shall show drainage pipe depth and location. Drainage pipe size shall be twice the inside diameter of the supply line. Protection on the drainage outlet shall be provided to prevent undesirable creatures from entering. (f) The vault cover shall be removable to allow full access to the vault. A minimum of two lifting points shall be provided. (g) An access door shall be installed in the vault cover on the testable side of the assembly. Approved doors shall be similar or equal to Bilco or Halladay and shall be a minimum of 24" x 24". (2) Minimum installation clearance dimensions shall be 30 inches between the assembly and corresponding wall and 12 inches on the opposite side, 8 inches on each end, 6 inches above the highest point and 12 inches under the assembly. Top of assembly shall not exceed 72 inches above finished grade. Unless prior approval by control authority. 13 i ` L Section 6.6 RECORDS shall be modified to read as follows: The consumer shall keep records for each assembly. Installation drawings, installer, test reports, manufacturer, model, serial number, date installed, schedule of preventive maintenance, test reports and technical data are the minimum record requirements. These records shall be maintained for a period not less than five years. Section 6.8 PENALTIES shall be modified to read as follows: A. Any consumer found in violation of any of the provisions of the Ordinance, shall be served by the Approving Authority with written notice stating the nature of the violation, describing the penalty applicable to the violation and providing a reasonable time limit for the satisfactory correction thereof. The offender shall, within the period of time stated in such notice, permanently cease all violations. The consumer may deliver by certified mail to the Approving Authority, within five (5) days of receipt of such notice, a written request for a hearing before the Approving Authority at which hearing the consumer shall be given an opportunity to show cause why the notice should be rescinded or modified. B. Any notice issued pursuant to this sub-section may provide a compliance directive mandating procedures to bring the consumer into compliance with the Program within the designated time; failure to comply with the compliance directive shall result in termination of water service. C. No action to terminate water service shall be final until the Approving Authority has given notice described herein and conducted the show cause hearing, if requested. D. However, if the Approving Authority determines that to continue to provide water service will endanger the public health, due to possible contamination of the Water System, water service to the property shall be immediately terminated. E. Any person violating the provisions of this Ordinance shall become liable to the BWU for any expense, loss or damage occasioned the BWU by reason of such violation. F. The listing of penalties in this Section shall not preclude other appropriate judicial remedies available to BWU for any violation of the Program. The BWU may petition any Court of competent jurisdiction to grant injunctive or other legal or equitable relief by reason of a violation. 14 I i • G. Any person maliciously, willfully, or negligently breaking, damaging, destroying, defacing, or tampering with any structure, appurtenance or equipment which is a part of any backflow prevention assembly or it's protective housing, shall be subject to all civil or criminal penalties which may be imposed under any applicable civil or criminal law of the State of Arkansas or the United States of America. • • 15 VOW 7.1 EFFECTIVE DATE This Ordinance shall be in full force and effect immediately following its passage, approval and publication, as provided by law. INTRODUCED: THE 23rd DAY OF_ Se=ptember 1997. FIRST READING: THE 23rd DAY OF September 1997. SECOND READING: THE 14th DAY OF October 1997. PASSED: THIS 28th DAY OF October 1997. AYES: 8 NAYS: 0 ABSENT: 0 NOT VOTING: 0 APPROVED by me this 28th day of_ October 1997. APPROVED BY: a Mayor ATTEST: %l' City Clerk PUBLISHED: Batesville Guard October 31. 1997 Publication Date L 16